Gebruik de reader hieronder om de Delfield CoolScapes GBSF1P-S Vriezer handleiding te lezen. U kunt de handleidingen direct op de pagina doorbladeren en de functies van onze reader gebruiken om alle belangrijke informatie over de installatie, bediening en het onderhoud van deze Delfield Vriezer te vinden.

Handleiding

Volledig scherm
Volledig scherm
Deel deze handleiding Delfield
Was deze handleiding nuttig?

Foutcodes

Hieronder vindt u de error codes voor de Delfield CoolScapes GBSF1P-S.

E1 sensor
KRITIEK

Box temperature sensor circuit is either open or shorted

Oplossing

Check resistance of sensor for open or short and replace sensor if either condition is found. If not, replace control.

E13 communication
WAARSCHUWING

Communication error between controller and display

Oplossing

Check for loose plugs on cable from control to display. If there are no loose plugs the display or control may need to be replaced.

E2 sensor
KRITIEK

Coil temperature sensor circuit is either open or shorted

Oplossing

Check resistance of sensor for open or short and replace sensor if either condition is found. If not, replace control.

E6 display
KRITIEK

Control has a defective potentiometer

Oplossing

Replace control.

Probleemoplossing

Praktische tips om de meest voorkomende problemen met Delfield CoolScapes GBSF1P-S op te lossen.

Cabinet not running power

Oorzaak: Fuse blown or circuit breaker tripped

Oplossing

Replace fuse or reset circuit breaker.

Cabinet not running power

Oorzaak: Power cord unplugged

Oplossing

Plug in power cord.

Cabinet not running temperature

Oorzaak: Thermostat set too high

Oplossing

Set thermostat to lower temperature.

Cabinet not running power

Oorzaak: Main power switch turned off

Oplossing

Turn main power switch on.

Cabinet not running maintenance

Oorzaak: Cabinet in defrost cycle

Oplossing

Wait for defrost cycle to finish.

Condensing unit runs for long periods or continuously performance

Oorzaak: Excessive amount of warm product placed in cabinet

Oplossing

Allow adequate time for product to cool down.

Condensing unit runs for long periods or continuously door

Oorzaak: Prolonged door openings or door(s) ajar

Oplossing

Make sure door(s) are closed when not in use. Avoid prolonged door openings.

Condensing unit runs for long periods or continuously door

Oorzaak: Door gasket(s) not sealing properly

Oplossing

Check gasket condition. Adjust door or replace gasket if necessary.

Condensing unit runs for long periods or continuously maintenance

Oorzaak: Dirty condenser coil

Oplossing

Clean the condenser coil.

Condensing unit runs for long periods or continuously maintenance

Oorzaak: Evaporator coil iced over

Oplossing

Turn unit off and allow coil to defrost. Make sure thermostat is not set too cold. Also, check gasket condition.

Cabinet temperature is too high temperature

Oorzaak: Thermostat set too high

Oplossing

Set thermostat to lower temperature.

Cabinet temperature is too high performance

Oorzaak: Poor air circulation in cabinet

Oplossing

Re-arrange product to allow proper air circulation.

Cabinet temperature is too high maintenance

Oorzaak: Exterior thermometer is out of calibration

Oplossing

Re-calibrate thermometer.

Cabinet temperature is too high performance

Oorzaak: Excessive amount of warm product placed in cabinet

Oplossing

Allow adequate time for product to cool down.

Cabinet temperature is too high door

Oorzaak: Prolonged door openings or door(s) ajar

Oplossing

Make sure door(s) are closed when not in use. Avoid prolonged door openings.

Cabinet temperature is too high maintenance

Oorzaak: Dirty condenser coil

Oplossing

Clean the condenser coil.

Cabinet temperature is too high maintenance

Oorzaak: Evaporator coil iced over

Oplossing

Turn unit off and allow coil to defrost. Make sure thermostat is not set too cold. Also, check gasket condition.

Cabinet is noisy noise

Oorzaak: Loose part(s)

Oplossing

Locate and tighten loose part(s).

Refrigerator is freezing product temperature

Oorzaak: Thermostat is set too low

Oplossing

Set thermostat to higher temperature.

Refrigerator is freezing product maintenance

Oorzaak: Dirty condenser coil

Oplossing

Clean the condenser coil.

Refrigerator is freezing product installation

Oorzaak: Not enough cabinet clearance for proper refrigeration system operation

Oplossing

Move cabinet or make other adjustments to gain proper cabinet clearances.

Compressor will not start power

Oorzaak: Low voltage to cabinet

Oplossing

Check and correct incoming voltage to cabinet.

Hulp

Heb je vragen over de Vriezer CoolScapes GBSF1P-S van Delfield? Stel ze direct aan onze expert! Je krijgt informatie, praktische tips en oplossingen op maat in slechts enkele seconden.

Hieronder vindt u handleidingen voor Vriezer die vergelijkbaar zijn met CoolScapes GBSF1P-S. Probeer ook alle Delfield Vriezer handleidingen te bekijken

Discussie

Laat een opmerking achter of stel een vraag

Doe mee aan de discussie

Stel een vraag over de handleiding of voeg een nuttig antwoord toe voor andere gebruikers.

Voer hier uw bericht in
Voer uw naam in
Voer uw e-mailadres in