Gebruik de reader hieronder om de Wolf MGK-130 Verwarmingsketel handleiding te lezen. U kunt de handleidingen direct op de pagina doorbladeren en de functies van onze reader gebruiken om alle belangrijke informatie over de installatie, bediening en het onderhoud van deze Wolf Verwarmingsketel te vinden.

Handleiding

Volledig scherm
Volledig scherm
Deel deze handleiding Wolf
Was deze handleiding nuttig?

Foutcodes

Hieronder vindt u de error codes voor de Wolf MGK-130.

1 water
KRITIEK

TBV excess temperature, water pressure too low, fault condensate pump

Oplossing

Check the system pressure. Check the heating circuit pump. Vent the system. Press the reset button. Check the condensate pump. Increase system pressure

11 other
WAARSCHUWING

Flame pretence

Oplossing

Press the reset button

12 sensor
WAARSCHUWING

Faulty flow sensor, gas pressure too low

Oplossing

Check lead. Check the flow sensor. Check gas pressure. Check the gas pressure switch settings

14 sensor
WAARSCHUWING

Cylinder sensor faulty

Oplossing

Check sensor and lead

15 sensor
WAARSCHUWING

Outside temperature sensor faulty

Oplossing

Check lead. Check the outside temperature sensor

16 sensor
WAARSCHUWING

Return sensor faulty

Oplossing

Check lead. Replace the return sensor

20 other
KRITIEK

Fault, gas valve "1"

Oplossing

Replace the gas combination valve

21 other
KRITIEK

Fault, gas valve "2"

Oplossing

Replace the gas combination valve

24 fan
KRITIEK

Gas fan fault

Oplossing

Check the gas fan supply cable and the gas fan; press the reset button

25 fan
KRITIEK

Gas fan fault

Oplossing

Check the gas fan supply cable and the gas fan; press the reset button

26 fan
KRITIEK

Gas fan fault

Oplossing

Check the gas fan supply cable and the gas fan; press the reset button

30 power
KRITIEK

CRC fault, gas condensing boiler

Oplossing

Switch the power supply OFF and ON. If unsuccessful, replace the control PCB

31 power
KRITIEK

CRC fault burner

Oplossing

Switch the power supply OFF and ON. If unsuccessful, replace the control PCB

32 power
KRITIEK

24VAC supply faulty

Oplossing

Check the gas fan

33 power
KRITIEK

CRC fault; default values

Oplossing

Replace the control PCB

34 other
WAARSCHUWING

CRC error BCC

Oplossing

Exchange parameter plug

35 other
WAARSCHUWING

BCC missing

Oplossing

Plug in the correct parameter plug

36 other
WAARSCHUWING

CRC error BCC

Oplossing

Exchange parameter plug

37 other
WAARSCHUWING

Wrong BCC

Oplossing

Plug in the correct parameter plug

38 other
WAARSCHUWING

BCC no. invalid

Oplossing

Exchange parameter plug

39 other
WAARSCHUWING

BCC system error

Oplossing

Exchange parameter plug

4 other
KRITIEK

No flame builds

Oplossing

Check the gas supply line and open the gas valve, if necessary. Check the ignition electrode and ignition cable. Press reset

41 water
WAARSCHUWING

Flow monitoring

Oplossing

Vent the heating system, check the system pressure. Check the heating circuit pump

43 performance
WAARSCHUWING

Burner starts >20 per hour

Oplossing

Check the flow rate; Header sensor must measure the common feed temperature of the cascade

5 other
KRITIEK

Flame failure during operation

Oplossing

Check CO values. Check ionisation electrode and cable. Press the reset button

50 other
INFORMATIE

Activation of the parameter plug

Oplossing

Press the reset button twice

52 other
INFORMATIE

Activation of the parameter plug

Oplossing

Press the reset button twice

6 temperature
KRITIEK

TW excess temperature

Oplossing

Check the system pressure. Vent the system. Increase pump speed

60 other
WAARSCHUWING

Ionisation current fluctuates

Oplossing

Clean siphon, check flue gas system, check ventilation air, check monitoring electrode

61 sensor
WAARSCHUWING

Ionisation current fails

Oplossing

Check monitoring electrode and lead

7 temperature
KRITIEK

TBA excess temperature, overpressure in the flue gas system

Oplossing

Clean the heat exchanger, check the flue gas system. Check ventilation air system. Check flue gas pressure switch

Probleemoplossing

Praktische tips om de meest voorkomende problemen met Wolf MGK-130 op te lossen.

LED constantly red other

Oorzaak: Ionisation cable shorted out or ionisation electrode earthed (casing)

Oplossing

Check ionisation cable and position of electrode to burner. Press the reset button

System pressure issues water

Oorzaak: Water pressure too low or system not properly vented

Oplossing

Check the system pressure. Vent the system. Increase system pressure if necessary

Temperature exceeds limit temperature

Oorzaak: Flow rate too high or heat exchanger blockage

Oplossing

Check the flow rate and heating circuit pump. Clean the heat exchanger if necessary

Gas supply issues other

Oorzaak: Gas valve closed or gas supply line blocked

Oplossing

Check the gas supply line and open the gas valve if necessary. Check gas pressure

Ignition problems other

Oorzaak: Faulty ignition electrode or ignition cable damaged

Oplossing

Check the ignition electrode and ignition cable. Replace if necessary

Veelgestelde Vragen

De meest gestelde vragen over de Wolf MGK-130.

Foutcode 1 geeft aan dat de TBV-temperatuur te hoog is, de waterdruk te laag is, of de condensaatpomp defect is. Controleer de systeemdruk, de verwarmingscircuitpomp, en lucht het systeem. Controleer ook de condensaatpomp.

Bij een flameout (foutcode 5) controleert u eerst de CO-waarden en de ionisatie-elektrode. Controleer ook de bekabeling van de ionisatie-elektrode en druk op de resetknop.

Een constant rode LED duidt op een kortsluiting in de ionisatiekabel of een onderbroken ionisatie-elektrode. Controleer de ionisatiekabel en de positie van de elektrode ten opzichte van de brander. Druk op de resetknop.

De boiler gebruikt verschillende NTC-sensoren (ketelvoeler, cilindersensor, retourvoeler, etc.). Deze sensoren hebben specifieke weerstandswaarden bij bepaalde temperaturen, zoals beschreven in de weerstandstabel.

Foutcode 26 geeft aan dat de gasventilatoren niet stoppen. Controleer de voedingskabel van de gasventilatoren en de ventilator zelf. Druk op de resetknop.

Als u foutcodes 34, 35, 36, 37, 38 of 39 krijgt, zijn er problemen met de parameteraansluiting (BCC). Vervang of steek de correcte parameteraansluiting opnieuw in.

Als er foutcodes 24, 25 of 26 zijn die betrekking hebben op gasventilatoren, controleert u de voedingskabel van de gasventilatoren en de ventilator zelf. Deze moeten het vereiste snelheidsniveau bereiken.

Foutcode 41 geeft aan dat de retourtemperatuur meer dan 25K hoger is dan de aanvoertemperatuur. Lucht het verwarmingssysteem, controleer de systeemdruk en de verwarmingscircuitpomp.

Hulp

Heb je vragen over de Verwarmingsketel MGK-130 van Wolf? Stel ze direct aan onze expert! Je krijgt informatie, praktische tips en oplossingen op maat in slechts enkele seconden.

Hieronder vindt u handleidingen voor Verwarmingsketel die vergelijkbaar zijn met MGK-130. Probeer ook alle Wolf Verwarmingsketel handleidingen te bekijken

Discussie

Laat een opmerking achter of stel een vraag

Doe mee aan de discussie

Stel een vraag over de handleiding of voeg een nuttig antwoord toe voor andere gebruikers.

Voer hier uw bericht in
Voer uw naam in
Voer uw e-mailadres in