Foutcodes

Hieronder vindt u de error codes voor de Mitsubishi MXZ-3HA50VF.

10-time blink temperature
WAARSCHUWING

Low discharge temperature protection - The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 39°C for more than 20 minutes.

Oplossing

Check refrigerant circuit and refrigerant amount. Refer to 12-6 'Check of LEV'.

11-time blink communication
KRITIEK

Communication error between P.C. boards, Current sensor, Zero cross detecting circuit, Converter, or Bus-bar voltage - Communication error occurs between the outdoor control P.C. board and outdoor power P.C. board for more than 10 seconds.

Oplossing

Check the connecting wire between outdoor control P.C. board and outdoor power P.C. board. Check the voltage of power supply. Replace the outdoor power P.C. board if necessary.

14-time blink other
KRITIEK

Stop valve - The current of compressor is power module is out of order.

Oplossing

Check the stop valve. Check the refrigerant circuit and the refrigerant amount.

17-time blink other
KRITIEK

Outdoor refrigerant system abnormality - A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.

Oplossing

Check for a gas leak in a connecting piping etc. Check the stop valve. Refer to 12-6 'Check of outdoor refrigerant circuit'.

2-time blink power
KRITIEK

Outdoor power system - Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started, or converter protection cut-out or bus-bar voltage protection cut-out operates 3 consecutive times within 3 minutes after startup.

Oplossing

Check the connection of the compressor connecting wire. Refer to 12-6 'How to check inverter/compressor'. Check the stop valve.

3-time blink sensor
KRITIEK

Discharge temperature thermistor, Defrost thermistor, Ambient temperature thermistor, Fin temperature thermistor, or P.C. board temperature thermistor - A thermistor shorts or opens during compressor running.

Oplossing

Refer to 12-6 'Check of outdoor thermistors'. Replace the outdoor control P.C. board if P.C. board temperature thermistor is faulty.

4-time blink power
KRITIEK

Overcurrent - 21 A current flows into power module.

Oplossing

Reconnect compressor connector. Refer to 12-6 'How to check inverter/compressor'. Check the stop valve.

5-time blink temperature
KRITIEK

Discharge temperature - The discharge temperature exceeds 115°C during operation.

Oplossing

Check refrigerant circuit and refrigerant amount. Refer to 12-6 'Check of LEV'.

6-time blink temperature
KRITIEK

High pressure - The outdoor heat exchanger temperature exceeds 70°C during cooling or the indoor gas pipe temperature exceeds 70°C during heating.

Oplossing

Check refrigerant circuit and refrigerant amount. Check the stop valve.

7-time blink temperature
WAARSCHUWING

Fin temperature or P.C. board temperature - The fin temperature exceeds 88°C during operation or the P.C. board temperature exceeds 67°C during operation.

Oplossing

Check around outdoor unit. Check outdoor unit air passage. Refer to 12-6 'Check of outdoor fan motor'.

8-time blink fan
KRITIEK

Outdoor fan motor - A failure occurs 3 consecutive times within 30 seconds after the fan gets started.

Oplossing

Refer to 12-6 'Check of outdoor fan motor'.

9-time blink other
KRITIEK

Outdoor control system - Nonvolatile memory data cannot be read properly.

Oplossing

Replace the outdoor control P.C. board.

Probleemoplossing

Praktische tips om de meest voorkomende problemen met Mitsubishi MXZ-3HA50VF op te lossen.

OPERATION INDICATOR lamp is blinking on and off to indicate an abnormality other

Oorzaak: Various abnormal conditions detected by the unit's monitoring system

Oplossing

Check how many times the OPERATION INDICATOR lamp is blinking on and off to identify the specific failure mode. Refer to the outdoor unit failure mode recall function table (12-2.3) to match the blinking pattern with the abnormal point.

Power supply voltage issue power

Oorzaak: Incorrect or unstable power supply voltage

Oplossing

Check the power supply voltage before troubleshooting any other issues.

Indoor/outdoor connecting wire miswiring connectivity

Oorzaak: Incorrect wiring between indoor and outdoor units

Oplossing

Check the indoor/outdoor connecting wire for miswiring before starting service work.

Connector and terminal connection issues connectivity

Oorzaak: Loose or improperly connected connectors and terminals

Oplossing

Check that the connector and terminal are connected properly. When disconnecting connectors, hold the connector housing and do not pull the lead wires.

P.C. board defects other

Oorzaak: Copper foil pattern disconnection, component bursting, or discoloration

Oplossing

Check the copper foil pattern for disconnection and the components for bursting and discoloration when the P.C. board seems to be defective.

Residual voltage hazard during servicing power

Oorzaak: Smoothing capacitor retains charge after power is turned off

Oplossing

Be careful of the residual voltage of the smoothing capacitor when removing electrical parts.

P.C. board damage during handling other

Oorzaak: Stress applied to components when removing the P.C. board

Oplossing

When removing the P.C. board, hold the edge of the board carefully and do not apply stress on the components.

Unit cannot operate properly after failure mode recall function other

Oorzaak: Failure mode recall function was not released after use

Oplossing

Make sure to release the failure mode recall function after it is set up. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

Veelgestelde Vragen

De meest gestelde vragen over de Mitsubishi MXZ-3HA50VF.

Zet de afstandsbediening in de failuremodus. Stel de temperatuur in op 25°C. Als het OPERATION INDICATOR lampje knippert met 0,5 secondes interval, is de buitenunit abnormaal. Controleer het knipperpatroon en raadpleeg de tabel voor buitenunit foutmodus heroproep (12-2.3) om het abnormale punt te bepalen.

Een knipperend OPERATION INDICATOR lampje geeft aan dat er een abnormale toestand is opgetreden. Het aantal keer dat het knippert (2-time blink, 3-time blink, enz.) geeft aan welk onderdeel of welke toestand problematisch is. Raadpleeg de failuremodus terugroepfunctietabel om het specifieke probleem te identificeren.

Zet het apparaat eerst uit met de afstandsbediening, bevestig dat de horizontale richtingaanduiding gesloten is, en zet vervolgens de stroomschakelaar uit en/of trek de stekker uit het stopcontact. Controleer de voedingsspanning en de bedrading van het binnenunit naar buitenunit op verkeerde aansluitingen.

Zorg ervoor dat u het vermogen uitschakelt voordat u het voorpaneel, de behuizing, het bovenpaneel en het printplaat verwijdert. Wees voorzichtig voor resterende spanning van smoothing-condensators wanneer elektrische onderdelen worden verwijderd.

Houd de rand van het bord voorzichtig vast en zorg ervoor dat u geen druk uitoefent op de componenten. Dit voorkomt beschadiging van de gevoelige elektronische onderdelen op het bord.

Houd altijd de connectorbehuizing vast. Trek niet aan de draadverbindingen. Dit kan beschadiging van de connectoren en draadverbindingen voorkomen.

Deze airconditioning heeft een failuremodus heroproepfunctie die abnormale omstandigheden kan onthouden. Zelfs als de LED-aanduiding verdwijnt, kunnen de opgeslagen foutdetails worden opgehaald door de failuremodus heroproepfunctie in te schakelen.

Na het herstellen van de foutieve onderdelen moet u de onthouden abnormale toestand uit het geheugen verwijderen. Zorg er ook voor dat u de failuremodus heroproepfunctie vrijgeeft, anders kan het apparaat niet correct werken.

Hulp

Heb je vragen over de Airco MXZ-3HA50VF van Mitsubishi? Stel ze direct aan onze expert! Je krijgt informatie, praktische tips en oplossingen op maat in slechts enkele seconden.

Hieronder vindt u handleidingen voor Airco die vergelijkbaar zijn met MXZ-3HA50VF. Probeer ook alle Mitsubishi Airco handleidingen te bekijken

Discussie

Laat een opmerking achter of stel een vraag

Doe mee aan de discussie

Stel een vraag over de handleiding of voeg een nuttig antwoord toe voor andere gebruikers.

Voer hier uw bericht in
Voer uw naam in
Voer uw e-mailadres in