Foutcodes

Hieronder vindt u de error codes voor de Gree CAS18HP230V1AC.

C5

System Configuration C5 1) No jumper cap inserted on the control board Malfunction 2) Incorrect or damaged jumper cap on control board

E1

System High Pressure E1 1) Over charged with refrigerant 2) Blocked or dirty outdoor coil

E2

Indoor Anti-Freeze Protection E2 3 flashes 1) Low return airflow and 1 sec Off 2) Indoor fan speed is too low

E3

Low Pressure Protection E3 9 flashes 1) Low on refrigerant and 1 sec Off 2) Pressure sensor is damaged

E4

Compressor High Discharge E4 7 flashes Please refer to the malfunction analysis (discharge Temperature Protection and 1 sec Off temperature, overload) in service manual

E5

Overcurrent Protection E5 5 flashes 1) Supply voltage is unstable and 1 sec Off 2) Supply voltage is too low and system load is too high

E6

Communication Malfunction E6 Continuous 1) Communication cable is mis-wired between indoor On and outdoor units

E7

Mode conflict (Indoor units E7 Operation status calling for simultaneously

E8

High Temperature E8 6 flashes 1) Incorrect refrigerant charge level Resistant Protection and 1 sec Off 2) Refrigerant metering device malfunction

E9

Cold Air Protection E9 1) Indoor coil has not reach minimum heating temperature 2) Indoor ambient is abnormally cold

F0

Refrigerant Leakage Protection F0 9 flashes 1) refrigerant leak(s) and 1 sec Off 2) Indoor coil temperature sensor no calibrated

F1

Indoor Ambient Temperature F1 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor ambient temperature sensor damaged

F2

Indoor Coil Temperature F2 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor coil temperature sensor damaged

F3

Outdoor Ambient Temperature F3 6 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor ambient temperature sensor damaged

F4

Outdoor Coil Temperature F4 5 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor coil temperature sensor damaged

F5

Outdoor Discharge Temperature F5 7 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Discharge temperature sensor damaged

F6

Compressor Overload Protection - F6 3 flashes 1) Incorrect refrigerant charge Frequency Decrease/Limit Mode and 1 sec Off 2) Metering device malfunction

F7

Oil Return Protection - Frequency F7 Normal function status code only Decrease/Limit Mode

F8

System Current Overload Protection - F8 1 flashes 1) Input voltage too low Frequency Decrease/Limit Mode and 1 sec Off 2) System pressure too low

F9

High Compressor Discharge F9 2 flashes and 4 flashes 1) Cooling load is too great Temperature - Frequency 1 sec Off and 1 sec Off 2) Outdoor ambient temperature too high

H1

Defrost Mode in Heating H1 Operation status Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose

H3

Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose and 1 sec Off 2) Refer to the malfunction analysis in Service Manual

H5

IPM Module Protection H5 4 flashes 1) IPM module over heating and 1 sec Off 2) Improper or Low voltage at the IPM module

H6

Indoor DC Fan Motor H6 1) Loose connections between fan motor and control board Malfunction 2) Fan motor or blower wheel bearings malfunction

H7

Compressor De-Synchronized H7 1) Compressor voltage is not balance Malfunction 2) Control board malfunction

L1

High DC Bus Voltage Protection PH 13 flashes 1) Supply voltage on L1 and N is above 265Vac and 1 sec Off 2) Capacitor on control board malfunction

L9

High Input Power Protection L9 9 flashes 1) Compressor malfunction and 1 sec Off 2) Power circuit malfunction

P5

Compressor Phase Current P5 1) IPM module malfunction Protection 2) Outdoor control board malfunction

P7

Module Temperature Sensor P7 Outdoor control board malfunction Malfunction

P8

Module Temperature Protection P8 1) Lack of thermal grease on IPM module 2) Heat sink (radiator) not tightly mounted

U1

Compressor Phase-Current U1 Outdoor control board malfunction Detection Malfunction

U3

DC Bus Voltage Dip U3 Outdoor control board malfunction Input Current Detection Malfunction U5 Outdoor control board malfunction

U5

Input Current Detection Malfunction U5 Outdoor control board malfunction The four-way valve is abnormal U7 Hardware malfunction

U7

The four-way valve is abnormal U7 Hardware malfunction Zero cross detection circuit U8 Hardware malfunction

U8

Zero cross detection circuit U8 Hardware malfunction malfunction(for indoor unit)

Hulp

Heb je vragen over de Airco CAS18HP230V1AC van Gree? Stel ze direct aan onze expert! Je krijgt informatie, praktische tips en oplossingen op maat in slechts enkele seconden.

Hieronder vindt u handleidingen voor Airco die vergelijkbaar zijn met CAS18HP230V1AC. Probeer ook alle Gree Airco handleidingen te bekijken

Discussie

Laat een opmerking achter of stel een vraag

Doe mee aan de discussie

Stel een vraag over de handleiding of voeg een nuttig antwoord toe voor andere gebruikers.

Voer hier uw bericht in
Voer uw naam in
Voer uw e-mailadres in